Small circuit breakers are either installed directly in equipment, or are arranged in a breaker panel.

The 10 ampere DIN rail mounted thermal-magnetic miniature circuit breaker is the most common style in modern domestic consumer units and commercial electrical distribution boards throughout Europe. The design includes the following components:

  1. Actuator lever - used to manually trip and reset the circuit breaker. Also indicates the status of the circuit breaker (On or Off/tripped). Most breakers are designed so they can still trip even if the lever is held or locked in the on position. This is sometimes referred to as "free trip" or "positive trip" operation.
  2. Actuator mechanism - forces the contacts together or apart.
  3. Contacts - Allow current to flow when touching and break the flow of current when moved apart.
  4. Terminals
  5. Bimetallic strip
  6. Calibration screw - allows the manufacturer to precisely adjust the trip current of the device after assembly.
  7. Solenoid
  8. Arc divider / extinguisher
-- article source :wikipedia---

Many different classifications of circuit breakers can be made, based on their features such as voltage class, construction type, interrupting type, and structural features.

Low voltage (less than 1000 V AC) types are common in domestic, commercial and industrial application, include:

  • MCB (Miniature Circuit Breaker)—rated current not more than 100 A. Trip characteristics normally not adjustable. Thermal or thermal-magnetic operation. Breakers illustrated above are in this category.
  • MCCB (Moulded Case Circuit Breaker)—rated current up to 1000 A. Thermal or thermal-magnetic operation. Trip current may be adjustable in larger ratings.
  • Low voltage power circuit breakers can be mounted in multi-tiers in LV switchboards.

The characteristics of LV circuit breakers are given by international standards such as IEC 947. These circuit breakers are often installed in draw-out enclosures that allow removal and interchange without dismantling the switchgear.

Large low-voltage molded case and power circuit breakers may have electrical motor operators, allowing them to be tripped (opened) and closed under remote control. These may form part of an automatic tranfer switch system for standby power.

Low-voltage circuit breakers are also made for direct-current (DC) applications, for example DC supplied for subway lines. Special breakers are required for direct current because the arc does not have a natural tendancy to go out on each half cycle as for alternating current. A direct current circuit breaker will have blow-out coils which generate a magnetic field that rapidly stretches the arc when interrupting direct current.

Medium-voltage circuit breakers rated between 1 and 72 kV may be assembled into metal-enclosed switchgear line ups for indoor use, or may be individual components installed outdoors in a substation. Air-break circuit breakers replaced oil-filled units for indoor applications, but are now themselves being replaced by vacuum circuit breakers (up to about 35 kV). Likehigh voltage circuit breakers described below, these are also operated by current sensing protective relays operated through current transformers. The charcteristics of MV breakers are given by international standards such as IEC 62271.

Electric power systems require the breaking of higher currents at higher voltages. High-voltage breakers may be free-standing outdoor equipment or a component of a gas-insulated switchgear line-up. Examples of high-voltage AC circuit breakers are:

  • Vacuum circuit breaker—With rated current up to 3000 A, these breakers interrupt the current by creating and extinguishing the arc in a vacuum container. These can only be practically applied for voltages up to about 35,000 V, which corresponds roughly to the medium-voltage range of power systems. Vacuum circuit breakers tend to have longer life expectancies between overhaul than do air circuit breakers.
  • Air circuit breaker—Rated current up to 10,000 A. Trip characteristics are often fully adjustable including configurable trip thresholds and delays. Usually electronically controlled, though some models are microprocessor controlled via an integral electronic trip unit. Often used for main power distribution in large industrial plant, where the breakers are arranged in draw-out enclosures for ease of maintenance.

The following animation shows how a conventional thermal/magnetic circuit breaker works. Current flowing through the circuit heats the bimetal current sensor, causing it to bend. When the amount of bending exceeds a limit, the armature is released and a spring forces the contacts to open. The load current also flows through a magnetic current sensor (coil) which creates a magnetic field that will trip the armature faster than the bimetal strip can respond when very large currents flow. When the contacts open, an arc will be generated that is dissipated in the arc channel. This opening to the outside prevents pressure buildup inside the breaker's case.
The conventional circuit breaker's performance is limited by:

  1. Slow response time of bi-metal current sensors.
  2. Mechanical tolerances that affect both the thermal and the magnetic trip limits.
  3. Inability to differentiate between arcing and normal start up transients due to large motors or incandescent lamps.
  4. The magnetic trip threshold must be set high to prevent nuisance tripping because:

    (a) normal transients require a time delay, not available with magnetic sensing, and
    (b) there is a strong interaction between thermal history (bi-metal strip position) and magnetic sensitivity.
----source : http://www.zlan.com/brk_info.htm----